IndustrialCalculating flow rate and pump head, the operating point and standby pumps.
Correct chiller pump selection is essential if a correctly sized chiller is actually to deliver its capacity. Too little flow leads to evaporator freezing risk and flow alarms; an oversized pump means wasted energy and noise. The right pump is selected on two basic values: flow rate and pump head.

The required water flow is found from the heat load and the temperature difference:
Flow (kg/s) = Heat load (kW) ÷ (4.18 × ΔT)
For example, for a 100 kW heat load and a 5 °C temperature difference, the required flow is about 100 ÷ (4.18 × 5) ≈ 4.8 kg/s, or roughly 17 m³ per hour. With water-glycol the specific heat is lower, so the required flow increases.
The total resistance the pump must overcome to circulate water through the circuit is expressed as pump head. It is the sum of:
In closed circuits the building height is not added to the head, because the water returns to the same level. In open circuits the static height must also be included.
The pump curve should cross the system resistance curve at the required flow. A pump selected close to its best efficiency point uses less energy and wears less.
For processes that must run without interruption, a standby pump is installed and the pumps run in rotation. Where the load varies, inverter-driven pumps can save energy by adjusting flow to demand. Good chiller pump selection always starts from an accurate heat load: see our chiller capacity calculation article and our site survey and design page.